Home 9 Service 9 Measurement Technology 9 Industrial Standard Signals

Industrial Standard Signals: ±10 V and 0(4)…20 mA

Industrial standard signals such as ±10 V, 0…20 mA and 4…20 mA are among the most important elements of analogue measurement technology. They are used to transmit physical variables not directly as a technical unit, but as a standardised electrical signal. This allows sensors, measuring transducers, I/O modules and controllers from different manufacturers to be combined and measured values to be processed reliably.

In practice, these analogue signal ranges are not only relevant for the pure transmission of measured values. The diagnostic capability of the signal, the detection of fault conditions and the conversion into the actual process variable are equally important. Modern modules therefore not only record signals, but also provide functions such as limit monitoring, fault signalling and user-specific scaling.

What are analogue standard signals in industrial measurement technology?

An analogue standard signal assigns a defined voltage or current range to a physical variable. The sensor therefore initially provides an electrical measured value, which is then recorded by an input module and converted into the required process variable.

Typical examples include:

  • 0…10 V for 0…100%
  • ±10 V for bipolar measured signals
  • 0…20 mA for linear process signals
  • 4…20 mA for industrial measuring circuits with fault detection

The advantage lies in standardisation. As long as all components involved support the same signal range, the measured value can be interpreted clearly and processed with little integration effort.

Voltage signals with ±10 V

Voltage signals are used when a measured value or control variable is transmitted as a potential difference. The ±10 V range is a typical standard for bipolar signals, i.e. for measured variables with both positive and negative value ranges.

A typical assignment is:

  • -10 V corresponds to the negative full-scale value
  • 0 V corresponds to the zero point or mid-point
  • +10 V corresponds to the positive full-scale value

Voltage signals are easy to record, but they are more sensitive to cable resistance, electromagnetic interference and potential differences than current interfaces. Clean wiring and suitable input circuitry are therefore important.

Current signals 0…20 mA and 4…20 mA

Current signals are particularly widespread in industrial measurement technology because they can be transmitted robustly even over longer cable lengths. Compared with voltage signals, cable resistance has a significantly lower impact on the measurement result in many applications.

The two common standards are:

  • 0…20 mA
  • 4…20 mA

Both signal ranges are linear, but they differ significantly in terms of their diagnostic capability.

Why 4…20 mA is important as a living zero

The valid measuring range of a 4…20 mA sensor does not start at 0 mA, but at 4 mA. This principle is known as a living zero. The lower measured value is therefore deliberately not placed at the electrical zero point.

he assignment is as follows:

  • 4 mA corresponds to the lower valid measured value
  • 20 mA corresponds to the upper valid measured value
  • 0 mA is not a valid process value and indicates a fault

This means that typical fault conditions such as cable breakage, sensor failure, interruption of the power supply or an interrupted signal path can be identified more clearly than with 0…20 mA or 0…10 V signals.

On modules such as the µCAN.4.ai-BOX or µCAN.6.ai-SNAP, this behaviour is monitored as standard: if the signal is outside the permissible range, the condition is detected as a fault and is output both via the CAN bus and via the LED signalling on the device.

Limit monitoring according to NAMUR

In addition to the nominal measuring range, the assessment of values falling below or exceeding limits is also important in practice. A measurement signal must not only be recorded, but also monitored with regard to its validity. In industrial applications, this is often done in connection with limit monitoring according to NAMUR, for a 4…20 mA signal according to the NAMUR NE43 standard. This allows the following conditions to be distinguished:
Current signal
Range
Comment
Imess < 3,6 mA
"Low" fault condition
Cable break, sensor defective
3,6 mA <= Imess < 3,8 mA
"Low" warning range
Alarm, sensor fault message
3,8 mA <= Imess <= 20,5 mA
Normal operating range
Nominal range 4 .. 20 mA
20,5 mA < Imess <= 21,0 mA
"High" warning range
Alarm, sensor fault message
Imess > 21,0 mA
"High" fault condition
Short circuit, sensor defective

Measurement technology solutions from MicroControl

You would like to get more information?

+49 2241 - 25 65 9 - 0

Write an email or give us a call.